Advantech BB-232OPDRI-PH

SPHINX i Europa
DK
  • AT
  • BE
  • DK
  • FR
  • DE
  • IE
  • IT
  • NL
  • ES
  • SE
  • CH
  • UK
Produktgrupper > Repeater > Advantech BB-232OPDRI-PH

Advantech BB-232OPDRI-PH

Heavy Industrial RS-232 Isolated Repeater

Advantech BB-232OPDRI-PH
4486_32931.png
4486_9849.png
4486_9850.png
4486_31732.jpg
4486_31734.jpg
  • egenskaberegenskaber
  • beskrivelsebeskrivelse
  • yderligere informationyderligere information
  • PDFPDF
  • IEEE-61850-3, IEEE-1613
  • NEMA TS2
  • -40 to 85°C Operating Temperature
  • Rugged IP30 Metal Panel Mount Case
  • 50G Shock, 4G Vibration
  • 2kV Triple Isolation
  • 10 to 48 VDC Input Power
The 232OPDRI-PH is our premium Heavy Industrial RS-232 Isolated Repeater. Designed for rugged industrial environments, it has been put through some of the most exacting compliance tests in the industry. Meeting the requirements of IEC 61850-3 and IEEE 1613, it is suitable for installation in electrical substations. These specifications are more stringent than the NEMA TS1/TS2 requirements for transportation applications. Powerful isolation on both data ports protects your equipment and data from damaging ground loops and surges. Additional isolation on the power supply circuits adds a third degree of protection.

Packaged in a rugged IP30 metal case, this repeater operates in wide temperature extremes. The panel mount form factor with DIN Rail mount option makes it easy to integrate into your control panel or other industrial equipment.

Installation and configuration is easy. Data is connected with a DB9 female connector (DCE) and a DB9 male connector (DTE). Power is connected through terminal block that accepts 10 to 48 VDC from any external source.

ProdGrafik

SPECIFICATIONS


SERIAL TECHNOLOGY

    Serial Connector
    DB9 F (DCE), DB9 M (DTE)

    Data Rate
    Up to 115.2 Kbps

    Isolation
    2 KV RMS, 1 minute



POWER

    Source
    External (Not Included)

    Power Connector
    2 Position Removable Terminal Block

    Input Voltage
    10 to 48 VDC (56 VDC Maximum)

    Power Consumption
    0.55 W (typical), 1.5 W (maximum)



TERMINAL BLOCKS

    Wire Size Accepted
    28 to 12 AWG

    Pitch
    5.08 mm

    Insulation Resistance
    ≥500 MΩ @ 500 VDC

    Maximum Torque
    5 Kg / cm



INDICATORS

    Power
    Red LED

    Data
    Green LED TD, RD, CTS, RTS



MECHANICAL

    Dimensions
    13.24 x 9.29 x 3.30 cm
    5.2 x 3.7 x 1.3 in

    Enclosure
    IP30 Metal, Panel Mount

    Weight
    0.46 lbs (208.65 grams)

    MTBF
    194712 Hours

    MTBF Calc. Method
    Parts Count Reliability Prediction



ENVIRONMENTAL

    Operating Temperature
    -40 to 85°C (-40 to 176°F)

    Storage Temperature
    -40 to 85°C (-40 to 176°F)

    Operating Humidity
    0 to 95% Non-condensing



REGULATORY

    Approvals
    FCC, CE, IEC 61850-3, IEEE 1613 UL C1 D2,
    File: E245458, NEMA TS2



IEC 61850-3 ELECTRO MAGNETIC INTERFERENCE SPECIFICATIONS
Test Description   Test Level Level
 61000-4-2  ESD  Enclosure Contact
 Enclosure Air
 8 kV
 15 kV
 4
 4
 61000-4-3   Radiated RFI  Enclosure Ports  10 V/m  3
 61000-4-4  Burst (Fast Transient)  Signal Ports
 DC Power Ports
 4 kV @ 2.5 Khz
 4 kV
 -
 4
 61000-4-5  Surge  Signal Ports
 DC Power Ports
 2 kV line to earth, 1 kV line to line
 2 kV line to earth, 1 kV line to line
 4
 3
 61000-4-6  Induced (Conductive) RFI  Signal Ports
 DC Power Ports
 10 V RMS
 10 V RMS
 3
 3
 61000-4-12  Damped Oscillatory  Signal Ports
 DC Power Ports
 2.5 kV common, 1 kV diff mode @ 1MHz
 2.5 kV common, 1 kV diff mode @ 1MHz
 3
 3
 61000-4-16  Mains Frequency Voltage  Signal Ports
 DC Power Ports
 30 V Continuous, 300 V for 1 s
 30 V Continuous, 300 V for 1 s
 4
 4
 61000-4-17  Ripple on DC Power Supply  DC Power Ports  10%  3
IEEE 1613 C37.90 ELECTROMAGNETIC INTERFERENCE SPECIFICATIONS
 C37.90.3  ESD  Enclosure Contact
 Enclosure Air
 8 kV
 15 kV
 -
 C37.90.2  Radiated RFI  Enclosure Ports  10 v/m  -
 C37.90.1  Fast Transient  Signal Ports
 DC Power Ports
 4 kV @ 2.5 kHz
 4 kV
 -
ENVIRONMENTAL SPECIFICATIONS
 60068-2-1  Cold Temperature  Test Ad  (-)40 C, 16 Hours  -
 60068-2-2  Dry Heat  Test Bd  (+)85 C, 16 Hours  -
 60068-2-30  Humidity (damp heat cycle)  Test Dd  90% (non-condensing) (+)55C, 6 Cycles  -
 IEC 600068-2-6  Vibration  Test Fc  4g  Class 2
 IEC 600068-2-27  Shock  Test Ea  50g  Class 2
 IEC 60068-2-32  Drop  -  6 faces, 1 corner, 3 edges, total 10 drops at 1 m  -



Kunder, der kiggede på dette produkt, kiggede også på
Accept all Reject Configure

This website uses cookies to provide the best possible experience. More information.